      System Abnormality, Refrigerant System Address Undefined

      Error Code             UH

      Applicable

      Models

      All indoor models

      REYQ-T

      Method of Error

      Detection

      Detect an indoor unit with no auto address setting.
      Error Decision

      Conditions

      The error decision is made as soon as the abnormality aforementioned is detected.
      Supposed

      Causes

      „ Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units

      „ Defective indoor unit PCB

      „ Defective outdoor unit PCB (A1P)

       

       