Mitsubishi Fault Code List

6603 – Bus circuit busy – check if indoor unit, Lossnay unit or anything else has been wired into TB7, instead of TB3
6607 – Communication issue – no response back from unit whilst system is operational
6608 – Communication error – loss of voltage or noise entering the transmission line
6700 – control communication error – R22 type unit connected onto M-Net circuit comms error
6701 – control communication error – R22 type unit connected onto M-Net circuit comms error
6702 – control duplicate address error – two or more R22 type units connected onto M-Net circuit with the same address
6750 – control communication error – R22 type unit connected onto M-Net circuit comms error
6751 – R/A thermistor fault (P1)
6752 – frost protection at I/C (P6)
6753 – Comms fault between O/C and I/C
6754 – drain fault (P5)
6755 – drain fault (P5)
6756 – frost protection at I/C (P6)
6757 – System error
6758 – Comms fault between I/C and O/C
6761 – R/A thermistor fault (P1)
6762 – TH2 fault check resistance (P2)
6763 – Comms fault between I/C and O/C
6764 – drain fault (P4)
6765 – drain fault (P5)
6766 – frost protection at I/C (P6)
6767 – comms fault between I/C and O/C
6771 – abnormality – high pressure abnormality or low pressure abnormality
6772 – abnormality – inner thermostat function, discharge temperature abnormality, shell thermostat function, over current protection
6773 – abnormality – radiator plate thermostat function
6774 – abnormality – outdoor thermistor abnormality
6775 – abnormality – pressure sensor abnormality, indoor/outdoor communication error
6776 – abnormality – over current shut-off
6777 – abnormality – system error
6778 – abnormality – normal
6779 – abnormality – refrigerant overcharge, abnormal voltage, abnormal CT sensor
6830 – Comms fault between I/C and R/C check connections to MA R/C and check for 12Vdc check R/C not set sub controller
6831 – MA R/C communication fault – check connections on TB15 or that the controller was removed while the I/C was powered
6832 – MA controller comms fault – check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings
6833 – MA controller comms fault check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings
6834 – MA Controller comms fault – check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings
6840 – A-Control E6/E8 fault – see Mr Slim fault code list
6841 – A-Control E7/E9 fault – see Mr Slim fault code list
6844 – A-Control EA fault – see Mr Slim fault code list
6845 – A-Control Eb fault – see Mr Slim fault code list
6846 – A-Control EC fault – see Mr Slim fault code list
7100 – Over capacity – (R2 150% index exceeded) (Y 130% index exceeded)
7101 – Capacity setting error – SW2 set wrong on indoors, SW5 on YHMA outdoor, (SW3-10 on older kit)
7102 – Error in number of connected units – loss of M-Net voltage (short or break), no power to BC, wrong SW5 setting on box, wrong box type
7105 – Address setting error – OC or BC addressed wrong
7106 – Attribute setting error – SW3-1 setting on a GUF
7107 – Port setting error – check if too much capacity on a single port, wiring SW2 setting, wrong SW14 setting or wrong units on a box when using multiple boxes
7110 – Check SW5-7 is correctly set
7111 – Remote control sensor fault – SW1 – 1 on and no controllers fitted or faulty remote controller
7113 – Function setting error – wrong SW5 setting or wrong resistors fitted on YHM-A
7117 – Model setting error – SW5 set wrong or wrong resistors in
7130 – Incompatible equipment on M-Net – check split with MAC 399 wired onto the TB5 line, not the TB7